Series L4 FLOTECT® Float Switch
Magnetically Operated Switch, Leak Proof Body, Explosion-Proof
Rugged and reliable the Series L4 Flotect® Float Switch operates automatically to indicate tank level. Perfect for starting or stopping pumps, opening or closing valves, or actuating level alarm signals. A unique magnetically actuated switching design gives superior performance. There are no bellows, springs, or seals to fail. Instead, the free-swinging float attracts a magnet within the solid metal switch body, actuating a snap switch by means of a simple lever arm. Float arm hinge design limits the arm angle to prevent vertical hang up.
Product Applications
- Direct pump control for maintaining level
- Automatic tank dump operations
- Control levels or provide alarms in sumps, scrubber systems, hydro-pneumatic tanks, low pressure boilers, and various water/wastewater treatment processes
- Level control
- Valve control
Starting at $738.90
Specifications
- Service:
- Liquids compatible with wetted materials.
- Wetted Materials:
- Float and Rod: 316 SS; Body: Brass or 316 SS standard; Magnet Keeper: 430 SS standard, 316 SS or nickel optional.
- Temperature Limits:
- 4 to 275°F (-20 to 135°C) standard, MT high temperature option 400°F (205°C) [MT option not UL, CSA, ATEX or IECEx]. ATEX and IECEx options: Ambient temperature -4 to 163°F (-20 to 73°C); Process temperature -4 to 163°F (-20 to 73°C).
- Pressure Limit:
- Brass body 1000 psig (69 bar), 316 SS body 2000 psig (138 bar). Standard float rated 100 psig (6.9 bar). For other floats, see options.
- Enclosure Rating:
- Weatherproof and Explosion-proof. **Listed with UL and CSA for Class I, Groups C and D; Class II, Groups E, F, and G. ATEX CE 2813 II 2 G Ex db IIB T6 Gb -20°C≤Tamb≤73°C. -20°C≤Process Temp≤73°C. EU-Type Certificate No.: KEMA 03 ATEX 2383. ATEX Standards: EN 60079-0:2012+A11:2013. IECEx Certified: For Ex db IIB T6 Gb -20°C≤Tamb≤73°C. -20°C≤Process Temp≤73°C. IECEx Certificate of Conformity: IECEx DEK 11.0071. IECEx Standards: IEC 60079-0:2011; IEC 60079-1:2014.
- Switch Type:
- SPDT snap switch standard, DPDT snap switch optional.
- Electrical Rating:
- UL, FM, ATEX and IECEx models: 10 A @ 125/250 VAC (V~). CSA models: 5 A @ 125/250 VAC (V~); 5 A res., 3 A ind. @ 30 VDC. MV option: 1 A @ 125 VAC (V~); 1 A res., .5 A ind. @ 30 VDC. MT option: 5 A @ 125/250 VAC (V~). [MT and MV option not UL, CSA, FM, ATEX or IECEx]
- Electrical Connection:
- UL and CSA models: 16 AWG, 6" (152 mm) long. ATEX and IECEx units: terminal block.
- Conduit Connection:
- 3/4" (19.05 mm) female NPT standard or M25 with -BSPT option.
- Process Connection:
- 1-1/2" (38.10 mm) male NPT or 1-1/2" (38.10 mm) male BSPT standard, 2-1/2" (63.50 mm) male NPT or 2-1/2" (63.50 mm) male BSPT standard optional floats.
- Mounting Orientation:
- Horizontal installation standard, optional vertical top mount.
- Deadband:
- 3/4" (19 mm) for standard float.
- Specific Gravity:
- 0.7 minimum with standard float. For other floats see Options/Accessories page.
- Weight:
- 4 lb 9 oz (2.07 kg).
- Compliance:
- ATEX, CE, CSA, FM, IECEx, UL**.
- **No Housing Option (-NH) has no approvals.
Features
- Superior performance due to unique magnetically-actuated switching design
- Long product life with no bellows, springs, or seals to fail
- Avoids clogs using a free-swinging float that attracts a magnet within the solid metal switch body, actuating a snap switch by means of a simple lever arm
- Prevents vertical hang up with float arm hinge design that limits the arm angle
Options
- -D DPDT Contacts.
- -MV Gold Plated Contact option for dry circuits.
- -MT High Temperature option rated 400°F (204°C).
- -TRI Time Delay Relay option for increasing flow with 2 SPDT contacts, adjustable from 0-1 to 0-31 minutes. (No listings or approvals.)
- -TRD Time Delay Relay option for decreasing flow with 2 SPDT contacts, adjustable from 0-1 to 0-31 minutes. (No listings or approvals.)
- -316 316SS Magnet Keeper option to replace standard 430SS.
- -AT ATEX approved construction.
- -SAA SAA approved construction.
- -TOP Top Mounted option for vertical flange installation (distance from flange face to centerline of float to be specified, 20" [508 mm] maximum).
- OPTIONAL FLOATS (all 2-1/2" spherical):
-50 304SS Float rated 50 psig (3.5 bar) and 0.5 min. s.g. (2-1/2" spherical).
-150 316SS Float rated 150 psig (10.3 bar) and 0.7 min. s.g. (2-1/2" spherical).
-300 304SS Float rated 300 psig (20.7 bar) and 0.7 min. s.g. (2-1/2" spherical).
Product Literature
Manuals
Catalog Pages
Product Data Sheet
Model Chart
EXAMPLE | L4 | SS-D-TOP | 50 | B1HC | Series L4-SS-D-TOP-50-B1HC Flotect® Float Switch, 316 SS body, DPDT, top mounted housing, 50 psi - 2-1/2" spherical float, with 2" hex type carbon steel bushing. |
SERIES | L4 | Flotect® Float Switch | |||
1ST SET OF OPTIONS (Select any or all) |
SS D TOP |
316SS Body (430 Magnet Keeper) DPDT Top Mounted Housing |
|||
2ND SET OF OPTIONS | 50 150 300 316 AT BSPT CI EPOXY IEC MT MV NH NI ST TBC TRD TRI W |
50 psi, 2-1/2" Spherical Float 150 psi, 2-1/2" Spherical Float 300 psi, 2-1/2" Spherical Float All 316SS Wetted Parts ATEX Approval BSPT Process Connection, M25 Conduit Cast Iron Housing Epoxy Coated Housing IECEX Approval High Temperature Gold Contacts No Housing Nickel 200 Vane/Vane Block Stainless Steel Tag Terminal Block Connection Time Delay Relay, Decreasing Flow Time Delay Relay, Increasing Flow Weld SST Threaded Flange or Bushing to SST Body |
|||
FLANGES/BUSHINGS | B1FC B1HB B1HC B1H4 B1HS B2FC B2F4 B2HC B2H4 B2HS B2HB B4HS F2C1 F2C3 F2C6 F2C9 F3C1 F3C3 F2S1 F2S3 F2S6 F3S1 F3S3 F4C1 F4C3 F4S1 F4S3 |
2" Flush Type Carbon Steel Bushing 2" Hex Type Brass Bushing 2" Hex Type Carbon Steel Bushing 2" Hex Type 304SS Bushing 2" Hex Type 316SS Bushing 2-1/2" Flush Type Carbon Steel Bushing 2-1/2" Flush Type 304SS Bushing 2-1/2" Hex Type Carbon Steel Bushing 2-1/2" Hex Type 304SS Bushing 2-1/2" Hex Type 316SS Bushing 2-1/2" Hex Type Brass Bushing 4" Hex Type 316SS Bushing 2" Carbon Steel 150# Flange 2" Carbon Steel 300# Flange 2" Carbon Steel 600# Flange 2" Carbon Steel 900# Flange 3" Carbon Steel 150# Flange 3" Carbon Steel 300# Flange 2" 316SS 150# Flange 2" 316SS 300# Flange 2" 316SS 600# Flange 3" 316SS 150# Flange 3" 316SS 300# Flange 4" Carbon Steel 150# Flange 4" Carbon Steel 300# Flange 4" 316SS 150# Flange 4" 316SS 300# Flange |
Questions
- Question
- What else needs to be specified when ordering an L4-TOP?
- Answer
- The vertical and horizontal lengths of the float arm.
- Question
- Why is the minimum specific gravity important on the float level switches?
- Answer
- If a medium has a lower s.g. than the rated minimum for a float, the float will sink through the media and the switch will not operate.
Write Your Own Review
Model | Description | Availability* | Price |
---|