Model PI Pressure To Current Transducer

Model PI Pressure To Current Transducer

Series EPTA Electro-Pneumatic Transducers

Low Cost, Selectable Input/Output, Manual Override
No longer available, see Series IP Current to Pressure Transducers or Series 2700/2800 Current to Pressure Transducers as suggested replacements.

California Residents:  Click Here for Proposition 65 WARNING.

Grouped product items
Model Description Availability* Qty Price

Specifications

Service:
Clean dry air or any inert gas.
Input Signal:
DC Current (4-20 mA) or DC Voltage (0-5/0-10/0-15).
Input Impedance:
Current: 250 ohms; Voltage: Infinite.
Output Signal:
Jumper selectable 0-10 psig (0-69 kPa), 0-15 psig (0-103 kPa), or 0-20 psig (0-138 kPa).
Feedback Output:
0 to 5 VDC.
Air Supply:
25 psig (172 kPa) maximum.
Air Flow:
750 scim.
Air Consumption:
0 scim normal operation, Fail-Safe model vents to 0 psi on power loss.
Accuracy:
±1.0% full scale @ room temperature; ±2.0% full scale @ 32 to 120°F (0 to 48.8°C).
Supply Voltage:
24 VDC (+10%/-5%) or 24 VAC (±10%) 50/60 Hz.
Supply Current:
180 mA maximum, 200 mA maximum on Fail-Safe model.
Temperature Limits:
Operating: 32 to 120°F (0 to 48.8°C); Storage: -20 to 150°F (-6.7 to 65.6°C).
Operating Humidity Range:
5 to 95%, non-condensing.
Pressure Connections:
1/4" O.D. (polyethylene tubing optimum).
Electrical Connections:
Plug-in block terminal type with 5 mm pin spacing.
Wire Size:
Up to one 14 AWG per terminal.
Weight:
EPTA-S0: 6.9 oz. (196 g), EPTA-S1: 9.2 oz. (261 g), EPTA-B: 14.5 oz. (411 g).

Features

  • Adjustable span and offset
  • Manual override
  • Field selectable output ranges
  • Not position sensitive

Product Literature

Manuals

Catalog Pages

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account