Series 2900 Current to Pressure Transducer

Series 2900 Current to Pressure Transducer

Representative image displayed of 2913-E|Actual product may vary

2913-E

Series IP Current to Pressure Transducers

Intrinsically Safe, NEMA 4X Enclosure, Field Reversible, Low Cost

The Series IP Current to Pressure Transducers converts a current input signal to a linearly proportional pneumatic output pressure. The features include built-in volume booster, low air consumption, field reversible (provides output which is inversely proportional to the input signal) and flexible zero and span adjustments. The rugged NEMA 4X enclosure allows splashdown and outdoor installation. The IP can be used for applications that require operation of valve actuators, pneumatic valve positioners, damper and louver actuators, final control elements, relays, air cylinders, web tensioners, clutches and brakes.

Product Applications

  • Applications that require the operation of valve actuators, pneumatic valve positioners, damper and louver actuators, final control elements, relays, air cylinders, web tensioners, clutches and brakes
Starting at $521.15
Grouped product items
Model Description Availability* Qty Price
IP-42 Current to pressure transducer, 4-20 mA input, 3-15 psi (20-100 kPa) output. 1-3 days*
$521.15
IP-43 Current to pressure transducer, 4-20 mA input, 3-27 psi (20-185 kPa) output. 1-3 days*
$523.70
IP-44 Current to pressure transducer, 4-20 mA input, 6-30 psi (40-200 kPa) output. 1-3 days*
$521.15

Specifications

Service:
Oil free, clean dry air filtered to 40 microns.
Input Signal:
4-20 mA.
Input Impedance:
IP-42: 180 ohms; IP-43 and IP-44: 220 ohms.
Air Pressure:
Minimum: 3 psig (21 kPa) above maximum output; Maximum: 100 psig (700 kPa).
Linearity:
<±0.75% of span.
Hysteresis:
<1% of span.
Repeatability:
<0.5% of span.
Supply Pressure Sensitivity:
<±0.1% of span per psig (<±0.15% of span per 10 kPa).
Power Requirements:
Loop powered.
Temperature Limits:
-20 to 140°F (-30 to 60°C).
Pressure Connections:
1/4" female NPT.
Electrical Connection:
1/2" female NPT.
Air Consumption:
0.03 SCFM (0.5 m³/h) typical.
Output Capacity:
4.5 SCFM (7.6 m³/h ANR) at 25 psig (175 kPa) supply; 12 SCFM (20 m³/h) at 100 psig (700 kPa) supply.
Relief Capacity:
2 SCFM (3.4 m³/h) at 5 psig (35 kPa) above 20 psig (140 kPa) setpoint.
Weight:
2.1 lb (0.94 kg).
Agency Approvals:
CE, FM.

Features

  • Built-in volume booster
  • Low air consumption
  • Flexible zero plus span adjustments
  • NEMA 4X enclosure
  • Field reversible

Product Literature

Manuals

Catalog Pages

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
Model Description Availability* Price