Series CDX Wall Mount Carbon Dioxide Transmitter
Measures up to 2000 PPM, Adjustable Output
No longer available.
Specifications
- Range:
- 0 to 2000 PPM.
- Accuracy:
- ±30 PPM or 3% of reading, whichever is higher. CO2 accuracy statement excludes standard gas used for calibration that has an accuracy of 2% and there is a potential digital to analog error of up to 1%.
- Temperature Dependence:
- 0.2% FS per °C (± 0.11% per °F).
- Stability:
- < 2% of FS over life of sensor (15 years).
- Pressure Dependence:
- .135% of reading per mm of Hg.
- Response Time:
- 5 s.
- Warm Up Time:
- < 2 min (operational), 10 min (max. accuracy).
- Temperature Limits::
- Operating: 32 to 122°F (0 to 50°C); Storage: -40 to 158°F (-40 to 70°C).
- Humidity Limits:
- 0 to 95% relative humidity, non-condensing.
- Power Requirements:
- 18 to 30 VAC RMS, 50/60 Hz, or 18 to 42 VDC, polarity protected.
- Power Consumption:
- .7 W @ nominal voltage of 24 VAC RMS.
- Sensor:
- Non-dispersive infrared (NDIR) absorption.
- Output:
- Analog, 0 to 5 V or 0 to 10 V jumper selectable (100 Ω output impedance), 4 to 20 mA (RL maximum 500 Ω).
- Housing:
- Flammability classification UL94 5VA.
- Weight:
- European Housing: 5.44 oz (154 g); North American Housing: 6.24 oz (177 g).
- Agency Approvals:
- CE, RoHS.