Series WWDP Differential Pressure Transmitter

Series WWDP Differential Pressure Transmitter

Series 616D Differential Pressure Transmitter

Series 616D Differential Pressure Transmitter

Series 645 Wet/Wet Differential Pressure Transmitter

±0.25% Accuracy, Quick Response, 2-Wire Design

Series 645 Wet/Wet Differential Pressure Transmitters are designed for use with compatible gases and liquids which can be applied to both the pressure and reference ports. Quick response capacitance sensor delivers a 4 to 20 mA output signal proportional to differential pressure with ±.25% accuracy. The Series 645 transmitters are ideal for process control, filter condition monitoring, refrigeration equipment, pump speed control, HVAC equipment, and liquid level measurement. For ease of installation and maintenance, order optional 3-valve manifold assembly. Bleed ports allow for total elimination of air in the line and pressure cavities.

Calibration Option available under Accessories.

California Residents:  Click Here for Proposition 65 WARNING.

Product Applications

  • Process control
  • Filter monitoring
  • Refrigeration equipment
  • Pump speed control
  • HVAC equipment
  • Liquid level measurement
Starting at $805.25
Filter By
Grouped product items
Model Description Availability* Qty Price
645-0 Wet/wet differential pressure transmitter, range 0-1 psid. 1-3 days*
$805.25
645-0-3V Wet/wet differential pressure transmitter with 3-valve manifold assembly, range 0-1 psid. 3-4 Weeks*
$1,330.00
645-1 Wet/wet differential pressure transmitter, range 0-2 psid. 1-3 days*
$805.25
645-1-3V Wet/wet differential pressure transmitter with 3-valve manifold assembly, range 0-2 psid. 4-5 Weeks*
$1,330.00
645-2 Wet/wet differential pressure transmitter, range 0-5 psid. 1-3 days*
$805.25
645-2-3V Wet/wet differential pressure transmitter with 3-valve manifold assembly, range 0-5 psid. 4-5 Weeks*
$1,330.00
645-3 Wet/wet differential pressure transmitter, range 0-10 psid. 1-3 days*
$805.25
645-3-3V Wet/wet differential pressure transmitter with 3-valve manifold assembly, range 0-10 psid. 3-4 Weeks*
$1,330.00
645-4 Wet/wet differential pressure transmitter, range 0-25 psid. 1-3 days*
$805.25
645-4-3V Wet/wet differential pressure transmitter with 3-valve manifold assembly, range 0-25 psid. 3-4 Weeks*
$1,330.00
645-5 Wet/wet differential pressure transmitter, range 0-50 psid. 1-3 days*
$805.25
645-5-3V Wet/wet differential pressure transmitter with 3-valve manifold assembly, range 0-50 psid. 4-5 Weeks*
$1,330.00
645-6 Wet/wet differential pressure transmitter, range 0-100 psid. 1-3 days*
$805.25
645-6-3V Wet/wet differential pressure transmitter with 3-valve manifold assembly, range 0-100 psid. 5-6 Weeks*
$1,330.00
645-10 Wet/wet differential pressure transmitter, range ±0.5 psid. 7-8 Weeks*
$805.25
645-11 Wet/wet differential pressure transmitter, range ±1 psid. 6-7 Weeks*
$805.25
645-12 Wet/wet differential pressure transmitter, range ±2.5 psid. 3-4 Weeks*
$805.25
645-12-3V Wet/wet differential pressure transmitter with 3-valve manifold assembly, range ±2.5 psid. 3-4 Weeks*
$1,330.00
645-13 Wet/wet differential pressure transmitter, range ±5 psid. 3-4 Weeks*
$805.25
645-13-3V Wet/wet differential pressure transmitter with 3-valve manifold assembly, range ±5 psid. 3-4 Weeks*
$1,330.00
645-14 Wet/wet differential pressure transmitter, range ±10 psid. 3-4 Weeks*
$805.25
645-14-3V Wet/wet differential pressure transmitter with 3-valve manifold assembly, range ±10 psid. 3-4 Weeks*
$1,330.00
645-15 Wet/wet differential pressure transmitter, range ±25 psid. 3-4 Weeks*
$805.25
645-15-3V Wet/wet differential pressure transmitter with 3-valve manifold assembly, range ±25 psid. 3-4 Weeks*
$1,330.00
645-16 Wet/wet differential pressure transmitter, range ±50 psid. 3-4 Weeks*
$805.25
645-16-3V Wet/wet differential pressure transmitter with 3-valve manifold assembly, range ±50 psid. 3-4 Weeks*
$1,330.00

Specifications

Service:
Compatible gases or liquids on both pressure and reference sides.
Wetted Materials:
17-4 PH stainless steel, 300 Series stainless steel, fluoroelastomer and silicone O-rings and bleed screw seals.
Accuracy:
±0.25% FS (RSS).
Temperature Limits:
Operating: 0 to 175°F (-22 to 80°C); Storage: -65 to 260°F (-54 to 126°C).
Pressure Limits:
(High side) 1 to 5 psi: 20 x FS, 10 to 25 psi: 10 x FS, 50 psi: 5 x FS, 100 psi: 2.5 x FS; (low side) 2.5 x FS.
Thermal Effects:
(includes zero and span) ±0.02% FS/°F, 30 to 150°F (-1 to 65°C).
Power Requirements:
11 to 30 VDC.
Output Signal:
4 to 20 mA, 2-wire.
Zero and Span Adjustments:
Adjustable, ±1 mA, non-interactive.
Response Time:
30 to 50 ms.
Loop Resistance:
0 to 1000Ω.
Electrical Connection:
Barrier strip terminal block with conduit enclosure and .875" (22 mm) diameter conduit opening.
Process Connection:
1/4"-18 female NPT.
Housing:
Stainless steel/aluminum, NEMA 4X (IP56).
Weight:
14.4 oz (0.4 kg).
Agency Approvals:
CE.

3-Valve Manifold Assembly
Manifold:
Brass.
Valve Type:
90° on/off.
Process Connection:
1/4"-18 female NPT.

Features

  • Versatile, high-accuracy device for liquid or gas supports designs requiring more precise measurements in support of application
  • Optional 3-way valve manifold supports simplifying installation or removal of transmitter without interrupting process

Support Libary

Manuals

Catalog Pages

Specifications

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
Model Description Availability* Price
NISTCAL-PT1 NIST traceable calibration certificate for pressure transmitters. NOTE: EQUAL CERTS WILL BE CHARGED PER UNITS PURCHASED. Less Than 1 Week*
$190.00