Series 651 Temperature Transmitter
RTD or Thermocouple Input, Zero and Span Adjust, Linearized 4 to 20 mA Signal
The Series 651 Temperature Transmitter is designed for use with 2 or 3 wire Pt100 RTDs or ungrounded Type K thermocouples. Thermocouple models 651TC are cold junction compensated, automatic 32 to 160°F (0 to 70°C) with upscale burnout.
Product Applications
- Process applications where a 4 to 20 mA signal is required
Starting at $188.85
Specifications
- Input:
- 2 or 3-wire Pt100 RTD (models 651A), or ungrounded Type K thermocouple (models 651TC).
- Output:
- 4 to 20 mA DC, linearized.
- Transmitter Type:
- 2-wire.
- Output Impedance:
- 700 Ω @ 24 VDC.
- Power Requirements:
- 10 to 32 VDC, reverse connection protected.
- Accuracy:
- ±0.2°C plus 0.2% reading (models 651A), ±0.1% FS plus cold junction errors (models 651TC).
- Temperature Drift:
- ZERO drift typical 0.02%/°C (0.09°F); SPAN typical 0.005%/°C 0.0036°F).
- Temperature Limits:
- Ambient: 32 to 122°F (0 to 50°C).
- Maximum Storage Temperature:
- 160°F (70°C).
- Response Time:
- 10 to 90% in 200 ms (models 651A), 70% in 2 ms (models 651TC).
- Agency Approvals:
- CE.
Features
- Various preset ranges available
- Pt100 or K type thermocouple models
- Standard temperature sensor head enclosure mounting
Approvals
Write Your Own Review
Model | Description | Availability* | Price | |
---|---|---|---|---|
A-709 |
Temperature Transmitter Enclosure. |
1-3 days* |
$59.80 |