Series GSTC Carbon Monoxide/Nitrogen Dioxide Gas Transmitter

Series GSTC Carbon Monoxide/Nitrogen Dioxide Gas Transmitter

Representative image displayed of CMT-DN-D|Actual product may vary

CMT-DN-D

Model CMS300 Carbon Monoxide Transmitter and Switch

Current/Voltage Selectable Output, Jumper Selectable SPDT Relay Contact

The Model CMS300 Carbon Monoxide Transmitter and Switch provides a field selectable current or voltage output that is proportional to the carbon monoxide concentration in underground parking garages, vehicle maintenance facilities, or mechanical rooms. An integral relay can be used for alarm conditions and is configured with preset jumper selectable ranges of 25, 60, or 150 PPM. Field calibration can be done by using Model GCK-200CO-2000CO2 calibration gas, Model A-507 calibration adapter, and the on board zero and span potentiometers.

Product Applications

  • Garage or loading dock ventilation
  • Vehicle maintenance facilities
  • Mechanical room monitoring
Starting at $197.10
Filter By
Grouped product items
Model Description Availability* Qty Price
CMS300 Carbon monoxide transmitter & switch, 0-300 PPM, 4-20 mA/2-10 V (maximum load 2K Ω) 1-3 days*
$197.10

Specifications

Sensor:
Electrochemical, 5 years typical lifespan.
Range:
0-300 PPM.
Output Drift:
<5% per year in air.
Temperature Effect:
±2% over range.
Coverage Area:
7,500 ft² (700 m²) or 50 ft (15 m) radius.
Accuracy:
±5 PPM or 5% of reading for 0-300 PPM (whichever is greater).
Resolution:
1 PPM.
Temperature Range:
-4 to 122°F (-20 to 50°C).
Storage Temperature:
For best sensor life, 32°F to 68°F (0 to 20°C).
Humidity Range:
15-90% RH constant; 0-99% RH intermittent.
Response Time:
<45 seconds to 90% of final value
Calibration:
15 turn span and zero adjustment potentiometers.
Housing:
UV resistant glass filledpolycarbonate.
Analog Output:
Jumper selectable 4 to 20 mA (loop powered) or 2 to 10 V (maximum load 2 kΩ).
Enclosure Rating:
IP64.
Weight:
1 lb (0.45 kg).
Switch Type:
Single-pole double-throw (SPDT).
Electrical Rating:
30 VAC/VDC. N/O = 5 A; N/C = 3 A
Set Point:
Jumper selectable 25, 60, or 150 PPM.
Set Point Differential/Hysteresis:
3% of scale.
Relay Action:
Factory set for direct acting.
Compliance:
Sensor is UL recognized component for ANSI/UL-2034, UL-2075, E340403, CE.

Features

  • Field selectable current or voltage analog outputs
  • Integral SPDT relay contact for low or high alarm
  • Jumper selectable alarm set points of 25, 60, or 150 PPM
  • UL recognized carbon monoxide sensing element
  • Field calibration kits

Product Literature

Manuals

Catalog Pages

Product Data Sheet

SlideShare

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
Model Description Availability* Price
A-GSTA-SE Security enclosure. 1-3 days*
$18.65
GCK-200CO-2000CO2 Gas Calibration Kit (GROUND SHIPMENTS ONLY) 1-3 days*
$726.55