Series 607 Differential Pressure Transmitter

Series 607 Differential Pressure Transmitter

Series MS Magnesense® Differential Pressure Transmitter

Monitors Pressure & Air Velocity
Grouped product items
Model Description Availability* Qty Price

Specifications

Service:
Air and non-combustible compatible gases.
Wetted Materials:
Consult factory.
Accuracy:
±1% for 0.25" (50 Pa), 0.5" (100 Pa), 2" (500 Pa), 5" (1250 Pa), 10" (2 kPa), 15" (3 kPa), 25" (5 kPa) ±2% for 0.1" (25 Pa), 1" (250 Pa) and all bidirectional ranges.
Stability:
±1% FS/year.
Temperature Limits:
0 to 150°F (-18 to 66°C).
Pressure Limits:
1 psi maximum, operation; 10 psi, burst.
Power Requirements:
10 to 35 VDC (2-wire); 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire).
Output Signals:
4 to 20 mA (2-wire); 0 to 5 V, 0 to 10 V (3-wire).
Response Time:
300 ms.
Zero & Span Adjustments:
Digital push button.
Loop Resistance:
Current output: 0-1250 Ω max; Voltage output: min. load resistance 1 kΩ.
Current Consumption:
40 mA max.
Display (optional):
4 digit LCD.
Electrical Connections:
4-20 mA, 2-wire: European Style Terminal Block for 16 to 26 AWG. 0-10 V, 3-wire: European Style Terminal Block 16 to 22 AWG.
Electrical Entry:
1/2" NPS Thread. Accessory: Cable Gland for 5 to 10 mm diameter cable.
Process Connection:
3/16" (5 mm) ID tubing. Maximum OD 9 mm.
Enclosure Rating:
NEMA 4X (IP66).
Mounting Orientation:
Diaphragm in vertical position.
Weight:
8.0 oz (230 g).
Compliance:
CE.

SlideShare

Model Chart

EXAMPLE MS 0 2 1 AT Series MS-021-AT Magnesense® Differential Pressure Transmitter, bidirectional unit, 4-20 mA output, low range 0.1, 0.25, 0.5" w.c. & 25, 50, 100 Pa, wall mount, with aluminum tag.
SERIES MS         Magnesense® Differential Pressure Transmitter
OUTPUT   0
1
2
3
6
7
8
9
      Bidirectional Unit, 4-20 mA
Positive Only Unit, 4-20 mA
Bidirectional Unit, 0-10 V
Positive Only Unit, 0-10 V
Bidirectional Unit, 0-5 V
Positive Only Unit, 0-5 V
Bidirectional Unit, 0-5 V Output 0-12VDC Input
Positive Only Unit, 0-5V Output 0-12 VDC Input
RANGE     1
2
3
4
5
    High Range 1, 2, 5" w.c. & 250, 500, 1250 Pa
Low Range 0.1, 0.25, 0.5" w.c. & 25, 50, 100 Pa
Piezo 10" w.c. & 2 kPa
Piezo 15" w.c. & 3 kPa
Piezo 25" w.c. & 5 kPa
MOUNTING       1
2
3
  Wall Mount
Duct Mount
Din Mounting Bracket
OPTIONS         AT
DJE
DJM
DS
GLD
LCD
NIST
ST
WO
Aluminum Tag
Velocity Mode Selectable Decimal Place (English Units)
Velocity Mode Selectable Decimal Place (Metric Units)
Dessicant Cover (not available)
Cable Gland Accessories Pack
Liquid Crystal Display
NIST Calibration Certificate
Stainless Steel Tag
LCD Cover w/o LCD Display

Note:  Not all model combinations are available.

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
Model Description Availability* Price
A-480 Plastic static pressure tip 1-3 days*
$2.15
A-481 Installer kit, (includes 2 static pressure tips and PVC tubing). 1-3 days*
$6.60
A-489 4" 303 SS straight static pressure tip with flange, 1/4" hose barb. 1-3 days*
$9.50
A-435 Field upgradeable LCD. Less Than 1 Week*
$62.95
SCD-PS 100 to 240 VAC/VDC to 24 VDC power supply 1-3 days*
$40.75
A-151 Cable gland for 5 to 10 mm diameter cable. 1-3 days*
$5.15
A-302F-A 303 SS Static pressure tip with mounting flange, for 3/16" I.D. rubber or plastic tubing. 4" insertion depth, includes mounting screws 1-3 days*
$12.40