Model KFD0 Galvanic Barrier

Model KFD0 Galvanic Barrier

Series MTL5541 Galvanic Barrier

Intrinsically Safe Isolators for Hazardous Locations

The Series MTL5541 Galvanic Barrier provides intrinsically safe isolation for communication with Dwyer® transmitters approved for use in hazardous areas. This galvanic barrier eliminates the need for a high integrity earth ground required when using shunt type diode type safety barriers. DIN rail mounting and plug-in signal and power connectors simplify installation and maintenance.

Product Applications

  • Electrically isolates pressure and level transmitters from unregulated circuits for intrinsically safe applications
Starting at $1,084.70
Grouped product items
Model Description Availability* Qty Price
MTL5541 Galvanic barrier 1-3 days*
$1,084.70

Specifications

Hazardous Area Input:
Signal range: 0 to 24 mA (including over-range); Transmitter voltage: 16.5 V at 20 mA.
Safe Area Output:
Signal range: 4 to 20 mA; Under/over-range: 0 to 24 mA;Load resistance: 0 to 360Ω @ 24 mA, or 0 to 450Ω @ 20 mA; Current sink: 600Ω max.; Maximum Voltage Source: 24 VDC; Output resistance: > 1 MΩ.
Power Requirement:
20 to 35 VDC.
Response Time:
Settles to within 10% of final value within 50 µs.
Current Consumption (20 mA signal):
51 mA @ 24V.
Maximum Power Dissipation (20 mA signal):
0.7 W @ 24 VDC, 1.0 W @ 24 VDC.
Isolation:
250 V RMS, tested at 1500 V RMS minimum, between safe- and hazardous-area terminals; 50 V between safe-area circuits and power supply.
Transfer Accuracy at 68°F (20°C):
Better than 15 µA.
LED Indicator:
Green: Power Indication.
Temperature Limits:
Operating: -6 to 140°F (-20 to 60°C); Storage: -40 to 176°F (-40 to 80°C).
Temperature Drift:
< 0.8µA/°C.
Humidity:
5 to 95% RH.
Mounting:
T-section 35mm DIN rail (7.5 or 15mm) to EN 50022.
Terminals:
Accommodate up to 2.5 mm2 stranded or single-core.
Safety Description:
Vo= 28 V, Io= 93 mA, Po= 651mW, Um= 253 RMS or DC.
Weight:
5.3 oz (150 g).
Compliance:
See table on catalog page.