±1.5% for 0.25" and ±0.25" w.c. ranges. Ranges 0.5" to 5" w.c. and
corresponding bi-directional (except ±2.5" w.c.) ±1%; All other ranges: ±0.5% @
77°F (25°C) including hysteresis and repeatability (after 1 hour warm-up).
Stability:
< ±1% per year.
Pressure Limits:
Ranges (uni- and corresponding bidirectional), ≤ 1 in w.c.: 9 psi; 2.5 and 5 in w.c.: 1.5 psi; 10 in w.c.: 3 psi; 25 in w.c.: 8 psi; 50 in w.c.: 15
psi; 100 in w.c.: 20 psi.
Temperature Limits:
32 to 140°F (0 to 60°C).
Compensated Temperature Limits:
32 to 140°F (0 to 60°C).
Thermal Effects:
0.020%/°F (0.036/°C) from 77°F (25°C). For 0.25" and ±0.25"
w.c. ranges: ±0.03%/°F (±0.054%/°C).
Power Requirements:
12 to 28 VDC, 12 to 28 VAC 50 to 400 Hz.
Power Consumption:
3 VA max.
Output Signal:
4 to 20 mA DC into 900 Ω max.
Zero & Span Adjustments:
Accessible via menus.
Response Time:
250 ms (damping set to 1).
Display:
Backlit 4 digit LCD 0.4" height LED indicators for set point and alarm
status.
Electrical Connections:
15 pin male high density D-sub connection. 18" (46 cm) cable with 10 conductors included.
A customer would like to get switching capability, local pressure indication, and a 4-20 mA output signal all in one device. Do we have a product to offer them?
Answer
Yes. Series' DH, DHII or DH3 possess high/low set points, digital gage display and 4-20 mA full scale output signal for air and compatible gas. Series' EDA, DPG-200, DPT, and MDPC possess high/low set points, digital gage display and 4-20 mA full scale output signal for compatible fluids.
Your Magnehelic gauge doesn't come with a calibration certificate, do you have any documentation for these gauges to meet these needs?
Answer
We have 3 options: (1) We can supply a Certificate of Conformance at no charge if you request that certificate at the time of order. The Certificate of conformance would state that each Magnehelic gauge is calibrated to meet the specifications stated on the spec sheet. (2) We offer a factory calibration “-FC” as an option that is a certificate of the standard calibration points at the time of manufacture, for a small fee. (3) We can also provide a NIST-traceable calibration for an extra charge per gage if that is required. To get the NIST-traceable calibration, you would simply add a “-NIST” to the end of your part number. NIST-traceable calibrations will come with the 6 point calibration certificate.
We recommend “periodic calibration” for our Magnehelic, though we leave the specific time-frame up to the end user, since different organizations have different requirements (i.e. government groups often require more frequent calibrations.) If you choose to have the NIST traceable calibration done, the NIST group (the National Institute of Standards and Technology) dictates yearly calibration and it will be printed on the certificate.
I am using DH3 Digihelic differential pressure controllers for my applications. The instruction says that "the Alarm can be reset by the RESET key on the front panel, or an external reset switch". For the second case (reset by external reset switch), could you let me know how to do it? The instruction doesn't provide any related detail. Thanks in advance.
Answer
Unfortunately, contrary to what was printed in the instruction manual, the DH3 does not have the ability for the alarm to be reset via an external reset switch, mainly due to the limited number of pins available in the electrical connector. This feature is only available in the DH and DHII series Digihelics.
Flat aluminum bracket for flush mounting (for Series A3000 Photohelic®, Series 4000 Capsuhelic®, Series 605, and Series 3000MR)
Less Than 1 Week*
$40.50
A-301
Static pressure tip, for 1/4" metal tubing connection.
1-3 days*
$14.50
A-302
Static pressure tip, for 3/16" and 1/8" ID plastic or rubber tubing.
1-3 days*
$13.75
A-302F-A
303 SS Static pressure tip with mounting flange, for 3/16" I.D. rubber or plastic tubing. 4" insertion depth, includes mounting screws
1-3 days*
$13.25
A-320-B1
Weatherproof enclosure, ABS, compatible with Series 3000MR/MRS Photohelic®, Series 605 Magnehelic®, Series DH3 Digihelic® (to fit, the casing on the electrical plug must be removed), Series 2000 Magnehelic® with medium and high pressure options
1-3 days*
$347.15
A-370
Flush mount bracket used with: Photohelic® 3000MR/MRS, Capsuhelic®, 631B Transmitter. Bracket is then surface mounted. Steel with gray hammertone epoxy finish.
1-3 days*
$48.50
A-489
4" 303 SS straight static pressure tip with flange, 1/4" hose barb.