Series RPME Room Pressure Monitor
Room Status Indication, Magnehelic® Gage Size
No longer available, see Series DHC Digihelic® Differential Pressure Controller as a suggested replacement.
Specifications
- Service:
- Air and non-combustible, compatible gases.
- Measurement Technology:
- Piezoresistive.
- Wetted Materials:
- Consult factory.
- Housing Material:
- Die cast aluminum case and SS bezel.
- Accuracy:
- ±0.5% RSS (includes non-linearity: ±0.49%, hysteresis: ±0.05% and non-repeatability: ±0.05%), or ±1% RSS (includes non-linearity: ±0.99%, hysteresis: ±0.05% and non-repeatability: ±0.05%).
- Pressure Limits:
- Ranges 0.5 and 1.0 in w.c: 9 psi; Ranges 2.5 and 5 in w.c.: 1.5 psi.
- Temperature Limits:
- 32 to 140°F (0 to 60°C).
- Compensated Temperature Limits:
- 32 to 140°F (0 to 60°C).
- Thermal Effects:
- 0.020%/°F (0.036/°C) from 77°F (25°C).
- Power Requirements:
- 12-28 VDC, 12-28 VAC 50 to 400 Hz.
- Power Consumption:
- 3 VA max.
- Output Signal:
- 4-20 mA DC into 900 Ω max.
- Zero and Span Adjustments:
- Accessible via menus.
- Response Time:
- 8 ms.
- Display:
- Backlit 4 digit LCD 0.4" height LED indicators for set point and alarm status.
- Electrical Connections:
- 15-pin male high density D-sub connection. 18" (46 cm) cable with 10 conductors included.
- Process Connections:
- 1/8" female NPT. Side or back connections.
- Mounting Orientation:
- Mount unit in vertical plane. Size: 4-3/4" (120.7 mm) OD x 2-21/32 (67.5 mm).
- Weight:
- 1.75 lb (794 g).
- SWITCH SPECIFICATIONS
- Switch Type:
- 2 SPDT relays.
- Electrical Rating:
- 1 A @ 30 VAC/VDC.
- Set Point Adjustment:
- Adjustable via keypad on face.
Features
- 2 SPDT relays allow for capability of local alarming and alarming to control system
- Automatic or manual alarm reset
- Visual LED alarms provide immediate local alert allowing corrective action to be taken quicker to eliminate the problem from becoming widespread
- Stores peak and valley process readings
- Same installation diameter as Magnehelic® gage which simplifies field upgrade to RPME room pressure monitor
- Password protected setup menu ensures no errors by untrained personnel
Options
- NIST Traceable Calibration Certificate
Product Literature
Manuals
Catalog Pages
Product Data Sheet
Approvals
Model Chart
RPME PRESSURE CONTROLLER RPME-X-X-OPT 1ST SYMBOL (1ST X) ACCURACY B 0.5% RSS C 1% RSS 2ND SYMBOL (2ND X) RANGE 003 0.5" w.c. 004 1" w.c. 005 2.5" w.c. 006 5" w.c. 014 -0.5-0-0.5" w.c. 015 -1-0-1" w.c. 016 -2.5-0-2.5" w.c. 017 -5-0-5" w.c. OPTIONS (OPT) -FC FACTORY CALIBRATION -NIST NIST TRACEABLE CALIBRATION CERTIFICATE
Write Your Own Review
Model | Description | Availability* | Price | |
---|---|---|---|---|
A-220 | Clear flexible vinyl tubing, 3/16" ID x 5/16" OD, lengths to 500'; 45 psi maximum pressure @ 73°F. | 1-3 days* |
$0.50 |
|
A-417A | Static pressure pickup. For use in clean rooms, 60 micron filter picks up static pressure. Stainless steel wall plate fits 2" x 4" electrical box. Sealed with foam gasket, screws included. Barbed brass fitting holds 1/8" to 3/16" ID tubing. | 1-3 days* |
$12.65 |
|
A-418A | Static Pressure Pickup. Room mount with Delta Style plastic enclosure fits 2" x 4" electrical box. Fine mesh screen hides static pressure pickup port. Clean connection to 1/8" to 3/16" I.D. tubing and pressure sensor. Sealed with foam gasket, screws included. | 1-3 days* |
$12.65 |
|
A-299 | Mounting bracket flush mount Magnehelic® gage in bracket. Bracket is then surface mounted . Steel with gray hammertone epoxy finish. 6.3" x 7.7" x 4.0", 1.30 lb. | 1-3 days* |
$41.55 |
|
A-300 | Flat aluminum bracket for flush mounting Magnehelic® gage. 6.8" x 6.0" x .1", .35 lb. | 1-3 days* |
$36.65 |
|
A-285 | Remote alarm annunciator with visible/audible alarm and acknowledge switch | 1-3 days* |
$331.05 |
|
A-465 | Flush mount space pressure sensor | 1-3 days* |
$13.95 |