Series AT-1800 ATEX/IECEx Approved Low Differential Pressure Switch

Series AT-1800 ATEX/IECEx Approved Low Differential Pressure Switch

Series 1620 Single and Dual Pressure Switch

Series 1620 Single and Dual Pressure Switch

Series 1950G Explosion-Proof Differential Pressure Switch

Explosion-proof, Weatherproof, Compatible with Natural Gases

Series 1950G Explosion-Proof Differential Pressure Switch combines the best features of the popular Dwyer® Series 1950 Pressure Switch with the benefit of natural gas compatibility. Units are rain-tight for outdoor installations, and are UL listed for use in Class I, Groups A, B, C, & D; Class II, Groups E, F, & G and Class III atmospheres, Directive 2014/34/EU (ATEX) Compliant for 2813 II 2G Ex db IIB+HT6, CSA & FM approved for Class I, Div. 1, Groups B, C, D; Class II, Div. 1, Groups E, F, G and Class III atmospheres. IECEx Ex db IIB+H T6 (-40°C<Ta<+60°C). The 1950G is very compact, about half the weight and bulk of equivalent conventional explosion-proof switches.
Easy access to the SPDT relay and power supply terminals is provided by removing the top plate of the aluminum housing. A supply voltage of 24 VDC, 120 or 240 VAC is required. A captive screw allows the cover to swing aside while remaining attached to the unit. Adjustment to the set point of the switch can be made without disassembly of the housing.

Product Applications

  • Natural gas applications
  • Process applications
  • All-weather applications
Starting at $530.40
Filter By
Grouped product items
Model Description Availability* Qty Price
1950G-0-B-120-NA Explosion-proof differential pressure switch, range .15-.50" w.c., approx. deadband @ min. set point .06, approx. deadband @ max. set point .11. 1-3 days*
$530.40
1950G-00-B-120-NA Explosion-proof differential pressure switch, range .07-.15" w.c., approx. deadband @ min. set point .04, approx. deadband @ max. set point .06. 1-3 days*
$530.40
1950G-1-B-120-NA Explosion-proof differential pressure switch, range .4-1.6" w.c., approx. deadband @ min. set point .11, approx. deadband @ max. set point .29 1-3 days*
$530.40
1950G-5-B-120-NA Explosion-proof differential pressure switch, range 1.4-5.5" w.c., approx. deadband @ min. set point .4, approx. deadband @ max. set point .9. 1-3 days*
$530.40
1950G-20-B-120-NA Explosion-proof differential pressure switch, range 4-20" w.c., approx. deadband @ min. set point 1.2, approx. deadband @ max. set point 3.0. 1-3 days*
$530.40
1950G-0-B-24-NA Explosion-proof differential pressure switch, range .15-.50" w.c., approx. deadband @ min. set point .06, approx. deadband @ max. set point .11. 1-3 days*
$530.40
1950G-00-B-24-NA Explosion-proof differential pressure switch, range .07-.15" w.c., approx. deadband @ min. set point .04, approx. deadband @ max. set point .06. 1-3 days*
$530.40
1950G-1-B-24-NA Explosion-proof differential pressure switch, range .4-1.6" w.c., approx. deadband @ min. set point .11, approx. deadband @ max. set point .29. 1-3 days*
$530.40
1950G-5-B-24-NA Explosion-proof differential pressure switch, range 1.4-5.5" w.c., approx. deadband @ min. set point .4, approx. deadband @ max. set point .9. 1-3 days*
$530.40
1950G-10-B-24-NA Explosion-proof differential pressure switch, range 3-11" w.c., approx. deadband @ min. set point .9, approx. deadband @ max. set point 1.8. 1-3 days*
$530.40
1950G-20-B-24-NA Explosion-proof differential pressure switch, range 4-20" w.c., approx. deadband @ min. set point 1.2, approx. deadband @ max. set point 3.0. 1-3 days*
$530.40

Specifications

Service:
Air and compatible combustible gases.
Wetted Materials:
Consult factory.
Temperature Limits:
0 to 140°F (-17 to 60°C). Note: Set point drift may occur with ambient temperature changes.
Pressure Limits:
45" w.c. (11.2 kPa) continuous; 10 psig (68.95 kPa) surge.
Enclosure Rating:
NEMA 3 (IP54), NEMA 7 and 9.
Switch Type:
1 Form C relay (SPDT).
Electrical Rating:
10 A, 120/240 VAC, 28 VDC. Resistive 50 mA, 125 VDC.
Power Requirements:
24 VDC ±10%. 120 or 240 VAC ±10% optional.
Electrical Connections:
Internal terminal block.
Process Connections:
1/8" female NPT.
Mounting Orientation:
Diaphragm in vertical position. Consult factory for other position orientations.
Set Point Adjustment:
Screw type on top of housing.
Weight:
2 lbs 15.7 oz (1.35 kg).
Compliance:
ATEX, CE, CSA, FM, IECEx, UL.

Features

  • Compatible with natural gas
  • External set point screw provides easy access that simplifies making adjustments without opening or disassembling enclosure
  • Easily accessible electrical connection simplifies the installation

Model Chart

EXAMPLE 1950G 00 B 120 AT Series 1950G-00-B-120-AT Explosion-proof Differential Pressure Switch, range 0.07-0.15" w.c., Buna-N diaphragm, 120 VAC supply voltage, with aluminum tag.
SERIES 1950G         Explosion-proof Differential Pressure Switch
RANGE   00
0
1
5
10
20
      0.07-0.15" w.c.
0.15-0.5" w.c.
0.4-1.6" w.c.
1.4-5.5" w.c.
3.0-11.0" w.c.
4.0-20.0" w.c.
DIAPHRAGM     B     Buna-N
INPUT VOLTAGE SUPPLY       120
240
24
  120 VAC
240 VAC
24 VDC
OPTIONS         AT
NA
PRESET
ST
Aluminum Tag
Non-ATEX Approved
Preset
Stainless Steel Tag

Questions

Question
Does Dwyer offer a fully UL/FM/CSA approved explosion proof pressure switch?
Answer
Yes. The 1950 and 1950G Series.
Question
What is the power consumption of a 24 VDC 1950G Pressure Switch?
Answer
The Current Draw for the 1950G 120mA @ 24VDC 30mA @ 120 VAC 15mA @ 240 VAC