NEMA 4X Enclosure, 0.25% FS Accuracy

Positive, negative and differential pressures can be measured within a full span accuracy of ±0.25 with the Series 616W Differential Pressure Transmitter. Units are enclosed in a polycarbonate case, rated NEMA 4X (IP66) and operate by sensing the pressure of air and compatible gases then sending a standard 4-20 mA output signal. Design enables operation in 2-wire current loops. A wide range of models are available factory calibrated to specific ranges. The span and zero controls are for use when checking calibration. They are not intended for re-ranging to a significantly different span. The LCD display allows local indication of pressure.

NIST CALIBRATION available in Product Configurator.

Product Applications

  • Dust collection
  • Outdoor HVAC
  • Roof-top equipment
Starting at $323.45
Filter By
Grouped product items
Model Description Availability* Qty Price
616W-2 Differential pressure transmitter, range 0-6" w.c., max. pressure 10 psig. Less Than 1 Week*
$323.45
616W-2-LCD Differential pressure transmitter, range 0-6" w.c., max. pressure 10 psig. Less Than 1 Week*
$443.05
616W-2M-LCD Differential pressure transmitter, range 0-1.5 kPa, max. pressure 68.9 kPa. Less Than 1 Week*
$443.05
616W-3 Differential pressure transmitter, range 0-10" w.c., max. pressure 10 psig. Less Than 1 Week*
$323.45
616W-3-LCD Differential pressure transmitter, range 0-10" w.c., max. pressure 10 psig. Less Than 1 Week*
$443.05
616W-3M-LCD Differential pressure transmitter, range 0-2.5 kPa, max. pressure 68.9 kPa. Less Than 1 Week*
$443.05
616W-4 Differential pressure transmitter, range 0-20" w.c., max. pressure 20 psig. Less Than 1 Week*
$323.45
616W-4-LCD Differential pressure transmitter, range 0-20" w.c., max. pressure 20 psig. Less Than 1 Week*
$443.05
616W-4M-LCD Differential pressure transmitter, range 0-5 kPa, max. pressure 137.8 kPa. Less Than 1 Week*
$443.05
616W-5 Differential pressure transmitter, range 0-40" w.c., max. pressure 20 psig. Less Than 1 Week*
$323.45
616W-5-LCD Differential pressure transmitter, range 0-40" w.c., max. pressure 20 psig. Less Than 1 Week*
$443.05
616W-5M-LCD Differential pressure transmitter, range 0-10.0 kPa, max. pressure 137.8 kPa. Less Than 1 Week*
$443.05
616W-6 Differential pressure transmitter, range 0-100" w.c., max. pressure 15 psig. Less Than 1 Week*
$323.45
616W-6-LCD Differential pressure transmitter, range 0-100" w.c., max. pressure 15 psig. Less Than 1 Week*
$443.05
616W-10B-LCD Differential pressure transmitter, range 5-0-5" w.c., max. pressure 10 psig. Less Than 1 Week*
$443.05
616W-20B-LCD Differential pressure transmitter, range 10-0-10" w.c., max. pressure 10 psig. Less Than 1 Week*
$443.05

Specifications

Service:
Air and non-combustible, compatible gases.
Wetted Materials:
Consult factory.
Accuracy:
±0.25% FS @ 77°F (25°C), display accuracy ±0.5%.
Thermal Effect:
±0.02% FS/°F (±0.036% FS/°C).
Stability:
±1% FS/yr.
Temperature Limits:
-4 to 158°F (-20 to 70°C).
Pressure Limits:
See Model chart on catalog page.
Power Requirements:
10 to 36 VDC (2-wire), 17 to 36 VDC, or isolated 21.6 to 33 VAC (3-wire).
Output Signal:
4 to 20 mA (2-wire), 0 to 5 VDC, or 0 to 10 VDC (3-wire).
Zero and Span Adjustments:
Digital push-button.
Response Time:
Instantaneous (default) or 3 s (selectable).
Loop Resistance:
Current output: 0-1250 Ω max; Voltage output: Min. load resistance 1 kΩ.
Current Consumption:
21 mA max. continuous.
Electrical Connections:
4-wire removable European style terminal block for 16 to 26 AWG.
Process Connections:
Barbed, dual size to fit 1/8" and 3/16" (3.12 and 4.76 mm) ID rubber or vinyl tubing.
Enclosure Rating:
NEMA 4X (IP66).
Mounting Orientation:
Any orientation.
Weight:
Without LCD 8.9 oz (253 g); with LCD 9.5 oz (269 g).
Compliance:
CE.

Features

  • NEMA 4X rated enclosure provides protection in harsh environments permitting outdoor monitoring or in areas where dust and particulate matter exists
  • Easy to read LCD display provides immediate local alerts allowing corrective action to be taken quicker to eliminate the problem from becoming widespread
  • Zero and span controls provides easy calibration checks and shorter installation time to get device running and monitoring

Model Chart

SERIES 616W TRANSMITTER

     616W-X-OPT 
          
          1ST SYMBOL (1ST X) RANGE
             2     0-6 INWC
             3     0-10 INWC
             4     0-20 INWC
             5     0-40 INWC
             6     0-100 INWC
             6B    3-0-3 INWC
            10B    5-0-5 INWC
            20B    10-0-10 INWC
             2M    0-1.5 KPA
             3M    0-2.5 KPA
             4M    0-5.0 KPA
             5M    0-25.0 KPA

          OPTIONS (OPT) KITS
             -AT      ALUMINUM TAG
             -COC     CERTIFICATE OF CALIBRATION
             -FC      FACTORY CALIBRATION
             -LCD     LIQUID CRYSTAL DISPLAY
             -NIST    NIST TRACEABLE CALIBRATION CERTIFICATE

Questions

Question
I am using a 616W-7-LCD, what tubing connections do we need to use with 1/8 or 3/16 tubing?
Answer
The 616W is designed to use either 1/8" or 3/16" ID tubing.