Representative image displayed of LCI132-11|Actual product may vary

LCI132-11

Representative image displayed of LCI508-00|Actual product may vary

LCI508-00

Series LCI132 Process Indicator

1/32 DIN, Fully Programmable

The Series LCI132 Process Indicator offer flexibility and value in a low cost, compact 1/32 DIN package. The shallow depth of these full size panel meters allows installation in panels only 2.76" (70 mm) deep with room to spare.

Product Applications

  • Display process values from various transmitters
Starting at $272.20
Grouped product items
Model Description Availability* Qty Price
LCI132-00 Process indicator, ±100 VDC; ±20 VDC; ±10 VDC; ±200 VDC; ±20 mA DC input, 120/240 VAC supply voltage. 17-18 Weeks*
$272.20
LCI132-01 Process Indicator, ±100 VDC; ±20 VDC; ±10 VDC; ±200 VDC; ±20 mA DC input, 24/48 VAC supply voltage. 1-3 days*
$272.20
LCI132-10 Process Indicator, ±100 VAC; 600 VAC; 5A (DC) 1A (DC); -199.9 to +600 VDC; ±100 VDC; -1.999 to 5A (DC) ±1A (DC) input, 120/240 VAC supply voltage. 11-12 Weeks*
$272.20
LCI132-11 Process Indicator, ±100 VAC; 600 VAC; 5A (DC) 1A (DC); -199.9 to +600 VDC; ±100 VDC; -1.999 to 5A (DC) ±1A (DC) input, 24/48 supply voltage. 11-12 Weeks*
$272.20

Specifications

LCI132-0X
Range:
Input Volts (DC): ±200 V, ±20 V, ±10 V; Input Amperes: ±100 mV, ±20 mA;
Resolution:
Input Volts (DC): 0.1 V, 0.01 V, 1 mV; Input Amperes: 0.1 mV, 0.01 mA; Input Impedance: Volts: 1 M Ω, mV: 100 M Ω, mA: 12.1 Ω.
LCI132-1X
Range AC:
Input Volts: 600.0, 100.0; Input Amperes: 5.000, 1.000;
Range DC:
Input Volts: -199.9, ±600.0, ±100.0; Input Amperes: -1.999, +5.000, ±1.000;
Resolution:
Input Volts: 0.1 V; Input Amperes: 1 mA Input Impedance: Volts: 3 M Ω (106), Amps: 12 m Ω (10-3).
Accuracy at 23ºC ±5ºC:
100/600 VDC 1/5 A DC; 600V/5A AC: ±(0.2% reading + 3 digits). 100 V / 1A AC: ±(0.4% reading + 4 digits).
Temperature Coefficient:
100 ppm/°C.
Warm Up:
5 minutes.
Power Supply and Fuses (DIN 41661) (Not supplied)
LCI132-X0:
85–265 VAC 50/60 Hz and 100-300 VDC: Fuse: 0.1A/ 250V.
LCI132-X1:
21-53 VAC 50/60Hz and 10.5-70 VDC: Fuse 0.5A/ 250V.
Display
LCI132-X0:
85–265 VAC 50/60 Hz and 100-300 VDC: Fuse: 0.1A/ 250V.
LCI132-X1:
21-53 VAC 50/60Hz and 10.5-70 VDC: Fuse 0.5A/ 250V.
Environmental
Operating Temperature:
-10 to 60°C.
Storage Temperature:
-25 to 85°C.
Relative Humidity (non condensed):
< 95% @ 40°C.
Panel Sealing:
NEMA 4X (IP66).

Features

  • Fits in 1/32 DIN panel cutouts
  • IP65 (NEMA 4X) front housing
  • Fully programmable
  • Various voltage and current inputs fits most processes

Product Literature

Manuals

Catalog Pages

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
Model Description Availability* Price