Series 668 Differential Pressure Transmitter

Series 668 Differential Pressure Transmitter

Series 608 Intrinsically Safe Differential Pressure Transmitter

Series 608 Intrinsically Safe Differential Pressure Transmitter

Series 616W Differential Pressure Transmitter

NEMA 4X Enclosure, 0.25% FS Accuracy

Positive, negative and differential pressures can be measured within a full span accuracy of ±0.25 with the Series 616W Differential Pressure Transmitter. Units are enclosed in a polycarbonate case, rated NEMA 4X (IP66) and operate by sensing the pressure of air and compatible gases then sending a standard 4-20 mA output signal. Design enables operation in 2-wire current loops. A wide range of models are available factory calibrated to specific ranges. The span and zero controls are for use when checking calibration. They are not intended for re-ranging to a significantly different span. The LCD display allows local indication of pressure.

NIST CALIBRATION available in Product Configurator.



⚠WARNING: This product can expose you to Styrene a chemical known to the State of California to cause Cancer and Bisphenol A (BPA) a chemical known to the State of California to cause reproductive toxicity. Click Here.

Product Applications

  • Dust collection
  • Outdoor HVAC
  • Roof-top equipment
Starting at $323.45
Filter By
Grouped product items
Model Description Availability* Qty Price
616W-2 Differential pressure transmitter, range 0-6" w.c., max. pressure 10 psig. Less Than 1 Week*
$323.45
616W-2-LCD Differential pressure transmitter, range 0-6" w.c., max. pressure 10 psig. Less Than 1 Week*
$443.05
616W-2M-LCD Differential pressure transmitter, range 0-1.5 kPa, max. pressure 68.9 kPa. Less Than 1 Week*
$443.05
616W-3 Differential pressure transmitter, range 0-10" w.c., max. pressure 10 psig. Less Than 1 Week*
$323.45
616W-3-LCD Differential pressure transmitter, range 0-10" w.c., max. pressure 10 psig. Less Than 1 Week*
$443.05
616W-3M-LCD Differential pressure transmitter, range 0-2.5 kPa, max. pressure 68.9 kPa. Less Than 1 Week*
$443.05
616W-4 Differential pressure transmitter, range 0-20" w.c., max. pressure 20 psig. Less Than 1 Week*
$323.45
616W-4-LCD Differential pressure transmitter, range 0-20" w.c., max. pressure 20 psig. Less Than 1 Week*
$443.05
616W-4M-LCD Differential pressure transmitter, range 0-5 kPa, max. pressure 137.8 kPa. Less Than 1 Week*
$443.05
616W-5 Differential pressure transmitter, range 0-40" w.c., max. pressure 20 psig. Less Than 1 Week*
$323.45
616W-5-LCD Differential pressure transmitter, range 0-40" w.c., max. pressure 20 psig. Less Than 1 Week*
$443.05
616W-5M-LCD Differential pressure transmitter, range 0-10.0 kPa, max. pressure 137.8 kPa. Less Than 1 Week*
$443.05
616W-6 Differential pressure transmitter, range 0-100" w.c., max. pressure 15 psig. Less Than 1 Week*
$323.45
616W-6-LCD Differential pressure transmitter, range 0-100" w.c., max. pressure 15 psig. Less Than 1 Week*
$443.05
616W-10B-LCD Differential pressure transmitter, range 5-0-5" w.c., max. pressure 10 psig. Less Than 1 Week*
$443.05
616W-20B-LCD Differential pressure transmitter, range 10-0-10" w.c., max. pressure 10 psig. Less Than 1 Week*
$443.05

Specifications

Service:
Air and non-combustible, compatible gases.
Wetted Materials:
Consult factory.
Accuracy:
±0.25% FS @ 77°F (25°C), display accuracy ±0.5%.
Thermal Effect:
±0.02% FS/°F (±0.036% FS/°C).
Stability:
±1% FS/yr.
Temperature Limits:
-4 to 158°F (-20 to 70°C).
Pressure Limits:
See Model chart on catalog page.
Power Requirements:
10 to 36 VDC (2-wire), 17 to 36 VDC, or isolated 21.6 to 33 VAC (3-wire).
Output Signal:
4 to 20 mA (2-wire), 0 to 5 VDC, or 0 to 10 VDC (3-wire).
Zero and Span Adjustments:
Digital push-button.
Response Time:
Instantaneous (default) or 3 s (selectable).
Loop Resistance:
Current output: 0-1250 Ω max; Voltage output: Min. load resistance 1 kΩ.
Current Consumption:
21 mA max. continuous.
Electrical Connections:
4-wire removable European style terminal block for 16 to 26 AWG.
Process Connections:
Barbed, dual size to fit 1/8" and 3/16" (3.12 and 4.76 mm) ID rubber or vinyl tubing.
Enclosure Rating:
NEMA 4X (IP66).
Mounting Orientation:
Any orientation.
Weight:
Without LCD 8.9 oz (253 g); with LCD 9.5 oz (269 g).
Compliance:
CE.

Features

  • NEMA 4X rated enclosure provides protection in harsh environments permitting outdoor monitoring or in areas where dust and particulate matter exists
  • Easy to read LCD display provides immediate local alerts allowing corrective action to be taken quicker to eliminate the problem from becoming widespread
  • Zero and span controls provides easy calibration checks and shorter installation time to get device running and monitoring

Model Chart

SERIES 616W TRANSMITTER

     616W-X-OPT 
          
          1ST SYMBOL (1ST X) RANGE
             2     0-6 INWC
             3     0-10 INWC
             4     0-20 INWC
             5     0-40 INWC
             6     0-100 INWC
             6B    3-0-3 INWC
            10B    5-0-5 INWC
            20B    10-0-10 INWC
             2M    0-1.5 KPA
             3M    0-2.5 KPA
             4M    0-5.0 KPA
             5M    0-25.0 KPA

          OPTIONS (OPT) KITS
             -AT      ALUMINUM TAG
             -COC     CERTIFICATE OF CALIBRATION
             -FC      FACTORY CALIBRATION
             -LCD     LIQUID CRYSTAL DISPLAY
             -NIST    NIST TRACEABLE CALIBRATION CERTIFICATE

Questions

Question
I am using a 616W-7-LCD, what tubing connections do we need to use with 1/8 or 3/16 tubing?
Answer
The 616W is designed to use either 1/8" or 3/16" ID tubing.
Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
Model Description Availability* Price