Model KFD0 Galvanic Barrier

Model KFD0 Galvanic Barrier

Series MTL7706/7787 Zener Barrier

Intrinsically Safe Barriers for Hazardous Locations

The MTL7706/7787 is an intrinsically safe (IS) shunt-diode barrier that can be used to communicate with and provide isolations for certain Dwyer® transmitters approved for use in hazardous areas. These barriers limit the amount of energy allowed to pass into the hazardous area, which inhibit ignition in flammable atmospheres.

Product Applications

  • Electrically isolates pressure and level transmitters from unregulated circuits for intrinsically safe applications
Starting at $383.90
Grouped product items
Model Description Availability* Qty Price
MTL7706 Intrinsically safe zener barrier 1-3 days*
$646.05
MTL7787 Intrinsically safe zener barrier. 1-3 days*
$383.90

Specifications

Transmitter Voltage:
16.2 V @ 20 mA with 250Ω load (negative w.r.t. earth); 11.0 V @ 20 mA with 500Ω load (negative w.r.t. earth).
Safe Area Output:
4 to 20 mA.
Load Resistance:
0 to 500Ω.
Power Requirement:
20 to 35 VDC w.r.t. earth.
Accuracy:
±2 µA under all conditions.
LED Indicator:
Green: Power Indication.
Temperature Limits:
Operating: -4 to 140°F (-20 to 60°C); Storage: -40 to 176°F (-40 to 80°C).
Humidity:
5 to 95% RH.
Terminals:
Accommodate up to 2.5 mm² stranded or single-core.
Safety Description:
28 µV, 300Ω, 93 mA.
Weight:
4.9 oz (140 g).
Agency Approvals:
See table on Catalog page.

Features

  • Approved for use in hazardous areas

Product Literature

Manuals

Catalog Pages

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
Model Description Availability* Price