Model 2-5001

Series 2-5000 Minihelic® II Differential Pressure Gage

Series AT-DHC ATEX/IECEx Approved Digihelic® Differential Pressure Controller

Series AT-DHC ATEX/IECEx Approved Digihelic® Differential Pressure Controller

Series RPMC StabiliSENSE™ Critical Room Pressure Monitor

Room Status Indication, Magnehelic® Gage Size
No longer available, see Series DHC Digihelic® Differential Pressure Controller as a suggested replacement.

Grouped product items
Model Description Availability* Qty Price

Specifications

Service:
Air and non-combustible, compatible gases.
Measurement Technology:
Capacitance cell.
Wetted Materials:
Consult factory.
Housing Material:
Die cast aluminum case and SS bezel.
Accuracy:
±0.25% RSS (includes non-linearity: ±0.24%, hysteresis: ±0.05% and non-repeatability: ±0.05%), or ±0.5% RSS (includes non-linearity: ±0.49%, hysteresis: ±0.05% and non-repeatability: ±0.05%).
Pressure Limits:
2 psig.
Temperature Limits:
32 to 140°F (0 to 60°C).
Compensated Temperature Limits:
32 to 140°F (0 to 60°C).
Thermal Effects:
0.030%/°F (0.050/°C) from 77°F (25°C).
Power Requirements:
12-28 VDC, 12-28 VAC 50 to 400 Hz.
Power Consumption:
3 VA max.
Output Signal:
4-20 mA DC into 900 Ω max.
Zero and Span Adjustments:
Accessible via menus.
Response Time:
8 ms.
Display:
Backlit 4 digit LCD 0.4" height LED indicators for set point and alarm status.
Electrical Connections:
15-pin male high density D-sub connection. 18" (46 cm) cable with 10 conductors included.
Process Connections:
1/8" female NPT. Side or back connections.
Mounting Orientation:
Mount unit in vertical plane. Size: 4-3/" (120.7 mm) OD x 2-21/32 (67.5 mm).
Weight:
1.90 lb (862 g).

SWITCH SPECIFICATIONS
Switch Type:
2 SPDT relays.
Electrical Rating:
1 A @ 30 VAC/VDC.
Set Point Adjustment:
Adjustable via keypad on face.

Features

  • Long term stable pressure measurements
  • 2 SPDT relays allow for local alarming and alarming to control system
  • Automatic or manual alarm reset
  • Visual LED alarms provide immediate local alert allowing corrective action to be taken quicker to eliminate the problem from becoming widespread
  • Stores peak and valley process readings
  • Same installation diameter as Magnehelic® gage which simplifies field upgrade to RPMC StabiliSENSE™ critical room pressure monitor
  • Password protected setup menu ensures no errors by untrained personnel

Product Literature

Manuals

Catalog Pages

Product Data Sheet

SlideShare

Approvals

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
Model Description Availability* Price
A-220 Clear flexible vinyl tubing, 3/16" ID x 5/16" OD, lengths to 500'; 45 psi maximum pressure @ 73°F. 1-3 days*
$0.50
A-285 Remote alarm annunciator with visible/audible alarm and acknowledge switch 1-3 days*
$331.05
A-299 Mounting bracket flush mount Magnehelic® gage in bracket. Bracket is then surface mounted . Steel with gray hammertone epoxy finish. 6.3" x 7.7" x 4.0", 1.30 lb. 1-3 days*
$41.55
A-300 Flat aluminum bracket for flush mounting Magnehelic® gage. 6.8" x 6.0" x .1", .35 lb. 1-3 days*
$36.65
A-417A Static pressure pickup. For use in clean rooms, 60 micron filter picks up static pressure. Stainless steel wall plate fits 2" x 4" electrical box. Sealed with foam gasket, screws included. Barbed brass fitting holds 1/8" to 3/16" ID tubing. 1-3 days*
$12.65
A-418A Static Pressure Pickup. Room mount with Delta Style plastic enclosure fits 2" x 4" electrical box. Fine mesh screen hides static pressure pickup port. Clean connection to 1/8" to 3/16" I.D. tubing and pressure sensor. Sealed with foam gasket, screws included. 1-3 days*
$12.65
A-465 Flush mount space pressure sensor 1-3 days*