Air Velocity Transmitter
This category contains sensors with an electrical transmission output for remote indication of air flow rate. Some products have LEDs while others have applications in clean room systems.
- Series 641 Air Velocity TransmitterAir Velocity Transmitter is ideal for monitoring air flow. Optional ...Starting at $676.00
- Series AVU Air Velocity TransmitterAir Velocity Transmitter ideal for a wide range of HVAC measurement an ...Starting at $249.00
- Series AVLV Air Velocity TransmitterAir Velocity Transmitter quickly and accurately measures air velocity ...Starting at $288.10
- Model 641B Air Velocity TransmitterAir Velocity Transmitter is used for dirty air flow applications. Ap ...Starting at $704.85
- Series AVPT Pencil Style Air Velocity TransmitterPencil Style Air Velocity Transmitter uses thermal anemometer technol ...Starting at $196.55
- Series 641RM Air Velocity Transmitter with Remote ProbeAir Velocity Transmitter with Remote Probe connects the sensing probe ...Starting at $676.00
MOST POPULAR
Questions
- Question
- We have recently replaced a Dwyer air velocity transmitter (PFS1300204) with a Dwyer Series 641. The new sensor works fine for only a few days and then starts reading almost no flow. These devices are used in an Air Scrubber application (exhaust stack). Is this the right application for the Series 641? I suspect that moisture might be the issue, but I cannot confirm.
- Answer
- I do not think you are using the 641 series air velocity transmitter in an appropriate application. Any moisture or particulates in the exhaust could be causing damage to the hot wire sensor, leading to the failure. The difference in the sensors is probably why you got longer life out of the PFS series, which unfortunately, is no longer available. The PFS series used a glass filled polyester sensor, which is a little more robust and can with stand the elements a little better. In your specific application, you might take a look at our 641B series which uses a heated mass flow sensor which can be used in dirty air environments.
- Question
- Is there a minimum duct size that this sensor can be used in?
- Answer
- The sensing element is about ¾” from the tip of the stem so the duct size would need to accommodate the entire sensing element. If being used in a smaller duct, you will want to verify that the flow range is within the operating range, 1000, 2000, 3000, or 4000 FPM.
- Question
- Can you use a display with the Modbus or BACnet options?
- Answer
- Yes, either the integral LCD Display, A-AVUL-LCD, or the remote display tool, A-435-A, can be used with Modbus or BACnet configurations.
- Question
- Is there a minimum duct size that this sensor can be used in?
- Answer
- The sensing element is about ¾” from the tip of the stem so the duct size would need to accommodate the entire sensing element. If being used in a smaller duct, you will want to verify that the flow range is within the operating range, 1000, 2000, 3000, or 4000 FPM.
- Question
- Can the AVPT output volumetric flow readings
- Answer
- No, the AVPT is configured to output air velocity readings in FPM or M/S only. Consider looking at the AVUL for a unit able to output volumetric air flow.